สายด่วน 096-060-3829
  sales@batteryupsgroup.com

เปลี่ยนแบตเตอรี่ Liebert GXT4-5000RT230

  • ผู้ผลิต: Emerson
  • รหัสสินค้า: GXT4-5000RT230
  • สถานะ: มีสินค้าในสต๊อก
  • สอบถามราคาได้ที่
    ***096-060-3829***


เปลี่ยนแบตเตอรี่ Liebert  GXT4-5000RT230
Battery Replacement  Liebert  GXT4-5000RT230
Battery Replacement GXT4-5000RT230

Technical Specifications
Liebert GXT4-5000RT230
Technology True Online
Capacity (VA / W) 5000VA/4000W
Dimensions, mm (in)  
Unit, W x D x H 430 x 574 x 217 (16.9 x 22.4 x 8.5)
Shipping, W x D x H 516 x 745 x 530 (20.3 x 29.3 x 20.9)
Weight, kg (lb)  
Unit 60 (132.2)
Shipping 75 (165.4); “E” model 71 (156.5)
Input AC Parameters  
Operating Frequency, Nom 50 or 60Hz (Factory Default is 50)
Factory Default VAC 230VAC
User-Configurable VAC 200/208/220/230/240VAC (May be modified using included configuration program)
Operating Voltage Range Without Battery Operation 176 - 280VAC
Maximum Allowable VAC 280VAC
Input Frequency Without Battery Operation 40 - 70Hz
Input Power Connection PD2-CE6HDWRMBS Standard
Output AC Parameters  
AC-AC Efficiency 92% AC-AC
Factory Default VAC 230VAC
Output Connections PD2-CE6HDWRMBS Standard
Frequency 50Hz or 60Hz, Nominal
Waveform Sinewave
Main Mode Overload >200% for 5 cycles; 151 - 200% for 1 seconds; 131-150% 10 seconds; 105 - 130% 1 minute
Internal Battery Charger  
Charger Current, Amperes 1.3
Battery Parameters  
Type Valve-regulated, non-spillable, lead acid
Quantity x V 20 x 12V
Recharge Time (Internal Batteries) 3 hr. to 90% capacity after full discharge into 100% load
Bypass Protection Limits  
Disable Bypass Operation If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass operation When the input frequency prevents synchronous operation
Environmental  
Operating Temperature, °C (°F) 0 to 40 (32 to 104) (no derating)
Storage Temperature, °C (°F) -15 to 50 (5 to 122)
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 1000m (3281 ft) at 25°C (77°F) without derating
Audible Noise <55 dBA, at 1 meter from the rear <50 dBA, at 1 meter from the front or sides
Agency  
Safety IEC62040-1:2008 version, GS mark
EMI/EMC/C-Tick EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6)
ESD IEC/EN EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient IEC/EN EN61000-4-4, Level 4, Criteria A
Surge Immunity IEC/EN EN61000-4-5, Level 3, Criteria A
Transportation ISTA Procedure 1E